GMS Instruments Header Containers

Valves

Clorius Controls

Safety Set SM6

The Clorius Safety Set SM6 is developed for all Clorius valves up to 150mm but may be used for other valve brands of corresponding size and function. It is consequently well suited for the modernisation of existing systems. The Clorius Safety Set SM6 is used for heating, cooling, ventilation and industrial systems, no matter whether the medium is water, steam or oil.

Price and delivery time will be given on request
Valve motor
Power supply 24 V AC / +10...-15%, 50/60 Hz
Consumption approx. 24 VA
Casing IP66
Cable union 2xM20 1xM16
Closing speed 15...30 sec.
Closing force 1100 N
Stroke 0...40 mm
Weight 5.6 kg
Control Box
Transformer 230/24 V AC, 10 VA, 50/60 Hz
Timer 10 sec.
External alarm Potential free switch
Fuse T 0.5 A / 250 V
Dual thermostat
Adjustable 35...95ºC
Overheat protection 95...110ºC
Thread ½ RG
Immersion-tube 110 mm

The Clorius Safety Set SM6 is developed for all Clorius valves up to 150mm but may be used for other valve brands of corresponding size and function. It is consequently well suited for the modernisation of existing systems. The Clorius Safety Set SM6 is used for heating, cooling, ventilation and industrial systems, no matter whether the medium is water, steam or oil.

Design

The Clorius Safety Set SM6 consists of a valve motor, a control box and a dual thermostat. A gear motor drives the valve motor. Stepping motor with SUT (Superior Universal Technology) electronic control unit and electronic load-dependant cut-off.

The valve motor is delivered for 24 V AC/DC. The build-in spring return ensures a closing time of max. 4 sec. By temperatures higher than 130ºC, a cooling unit (1-0152285) is to be mounted between valve and motor.

All gear wheels and bearings are lifetime lubricated. Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel. The spring return is released when the power disappears from the holding coil, closing the valve completely. A timer in the control box ensures that the motor is not turned on again before 10 sec. after a spring return release. This function protects against starting the motor before the spring return function has terminated.

The control box contains:

  • 230/24 V AC transformer for the valve motor
  • 10 sec. timer for the spring return
  • Potential free alarm switch
  • Terminal blocks for connections to the valve motor, the dual
  • Thermostat, other safety equipment, an alarm, and power
  • Build-in fuse protecting against overload and short-circuiting

The dual thermostat is set to the normal close-down temperature, e.g., 90ºC, where the valve is to be closed. It further includes an overheating thermostat for spring return emergency close-down at 105ºC. This ensures correct function, even if, e.g., the normal thermostat should fail. For additional safety, the overheating thermostat has to be reset manually after a break.

Request an offer

RECEIVE A QUOTE WITHIN 3 HOURS ON BUSINESS DAYS

  • 1. Product request

    • or
  • 2. Your information

  • This field is for validation purposes and should be left unchanged.

GMS_Instruments_Delivery_Van_Driving

Want more information?

Get in touch with Bart our Clorius specialist

Bart

Bart de Haan

Managing Director

GMS-Instruments-brochure-2024

Product catalog

General contact

Driemanssteeweg 190
3084 CB Rotterdam
The Netherlands
GMS-Instruments-hq